Inspection
Inspection Details
Equipment ID
22603
22603
Inspection Date
5/1/2019
5/1/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
370
370
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
b7bb009c-3c1b-48bb-b3d7-a2a12b28f6bf
b7bb009c-3c1b-48bb-b3d7-a2a12b28f6bf
Location
BJC Healthcare
13001 N. OUTER 40, ST. LOUIS, MO
13001 N. OUTER 40, ST. LOUIS, MO
Owner
Attn: Stacey Allen
BJC Healthcare c/o Cushman & Wakefield
8300 EAGER RD STE 600D, SAINT LOUIS, MO 63144
Phone: (314) 996-5346
Email: Stacey.Allen@cushwake.com
BJC Healthcare c/o Cushman & Wakefield
8300 EAGER RD STE 600D, SAINT LOUIS, MO 63144
Phone: (314) 996-5346
Email: Stacey.Allen@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Oil usage, findings for firefighters' service operation tests, and other records, along with instructions for location such records shall be posted. | 6/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. (Unable to transfer power on date of inspection) | 6/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The monthly fire service testing log is not being filled out. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. Emergency power is scheduled to be tested separately this evening. | 6/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Fire service operation shall be tested as required. Fire service is scheduled to be tested separately this evening. | 6/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 2015. The overspeed valve shall be scheduled for the category 5 test on or before the next annual inspection. | 6/26/2024 |