Inspection
Inspection Details
Equipment ID
14626
14626
Inspection Date
5/15/2019
5/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Leo
David Leo
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
10f6ca3a-6727-43f7-91aa-d211de40e816
10f6ca3a-6727-43f7-91aa-d211de40e816
Location
Saint Louis Galleria
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Owner
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Billing
Attn: General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117-1159
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.14 | No | No | Clean down | 1/15/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Unable to verify if wiring diagrams provided at location are job specific diagrams. Provide unit specific wiring diagrams. | 12/5/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Multiple step tread cleats are damaged, forming a "sharp knife edge". Damaged step treads shall be replaced to conform to code. | 9/23/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | All demarcation lighting shall work. | 9/23/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Escalator machine space shall be kept clean and free from excessive debris (dust, dirt, oil, etc.). Clean lower pit. | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Current state operating permit shall be displayed. | |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete: Comb impact & step index testing still needs to be performed and witnessed. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | 8.6.8.6.5 - Multiple step tread cleats are damaged, forming a sharp "knife-edged". Damaged steps treads should be replaced to conform to code. (2nd Notice) | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | All demarcation lighting shall work. (2nd Notice) | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Reversal switch shall work properly. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Escalator machine spaces/pits shall be kept clean and free from excessive debris, dirt, dust, oil, etc. Clean upper and lower pits. (2nd Notice) | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | A current MO State operating certificate shall be obtained and displayed. |