Inspection
Inspection Details
Equipment ID
17854
17854
Inspection Date
5/20/2019
5/20/2019
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
N/A
N/A
External ID
9b59debe-0d32-48e1-a2f2-3e4a6014f9a2
9b59debe-0d32-48e1-a2f2-3e4a6014f9a2
Location
Independence Regional Health Center
19600 E 39TH ST S, INDEPENDENCE, MO
19600 E 39TH ST S, INDEPENDENCE, MO
Owner
Attn: Center Point Medical Center
Center Point Medical Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057
Phone: (816) 698-7093
Email: David.Riggs@hcamidwest.com
Center Point Medical Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057
Phone: (816) 698-7093
Email: David.Riggs@hcamidwest.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | no maint records on site | 2/29/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | couldnt test emg. power at time of test | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25 | new mach. no rope gripper | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report from lic. pro. eng.on support of new mach. room floor an mach. beams | 2/29/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | standby power test didnt work properly | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | no rope gripper or emg. brake | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | no mcp on site | 2/29/2024 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report by prof. eng. on machroom floor over hoistway | 2/29/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt. on display | 6/24/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | couldnt test emg power at this time scheduled for april | 2/29/2024 | |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report on mach. room floor by prof eng. | 2/29/2024 | ||
| A17.1-2016 : Elevators | 2.18 - Traction drive machines | 8.7.2.25.1 | x | no emg. brake installed as per code | 2/29/2024 | |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | platform guard less than 48 ins. | 6/12/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt. displayed | 6/24/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt displayed | 6/24/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | emg power couldnt be tested at time of insp | 3/6/2024 | |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | need 48 in platform Guard or a variance | 6/12/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | x | Zero counterweight runby, shorten ropes. |