Inspection
Inspection Details
Equipment ID
24159
24159
Inspection Date
5/10/2019
5/10/2019
Inspection Type
New Installation
New Installation
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jacob Williams
Jacob Williams
Relief Valve Pressure
Slide
4"
4"
Governor Rope Pull
40/190
40/190
Door Closing Force
23
23
External ID
0bef023c-8d58-4ca8-865e-e535650df3c0
0bef023c-8d58-4ca8-865e-e535650df3c0
Location
South Grand Apartments
2232 S GRAND BLVD, SAINT LOUIS, MO
2232 S GRAND BLVD, SAINT LOUIS, MO
Owner
Altus Bemisont LLC c/o Altus Properties LLC
231 S BEMISTON AVE STE 650, SAINT LOUIS, MO 63105-1956
231 S BEMISTON AVE STE 650, SAINT LOUIS, MO 63105-1956
Billing
Attn: Altus Bemisont LLC c/o Altus Properties LLC
231 S BEMISTON AVE STE 650, SAINT LOUIS, MO 63105-1956
231 S BEMISTON AVE STE 650, SAINT LOUIS, MO 63105-1956
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | Provide code compliant lighting (19fc) at controller. | 5/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.11 - Hoistway smoke control | 8.11.2.1.3(q) | Yes | No | Provide a vent at top of hoistway to open upon activation of Elevator Phase 1 initiation device. | 5/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Provide testing of all elevator related smoke detectors. | 5/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Provide testing of all elevator related heat detectors, including top floor lobby. | 5/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Fire gibs shall be installed. | 8/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The keyed stop switch on the COP shall be over-ridden on Phase 1 fire service. | 8/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs shall be installed. | 10/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Third floor hoistway door is missing fire gibb. | 11/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. The form is present in the MCP, but hasn't been logged monthly. | 12/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | Fire service buzzer shall work on 1 recall. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove exess debris. |