Inspection
Inspection Details
Equipment ID
19079
19079
Inspection Date
6/6/2019
6/6/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
da76f6ea-9cc3-4308-b877-8d36969eab63
da76f6ea-9cc3-4308-b877-8d36969eab63
Location
First Inn- Branson
2719 W 76 COUNTRY BLVD, BRANSON, MO
2719 W 76 COUNTRY BLVD, BRANSON, MO
Owner
Ganesham Tahoe
2719 W 76 COUNTRY BLVD, BRANSON, MO 65616-2169
2719 W 76 COUNTRY BLVD, BRANSON, MO 65616-2169
Billing
Attn: First Inn- Branson
2719 W 76 COUNTRY BLVD, BRANSON, MO 65616-2169
2719 W 76 COUNTRY BLVD, BRANSON, MO 65616-2169
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Clean up the oil and debris from the pit floor. | 8/20/2019 | ||
conversion | conversion | n/a | Replace the burnt up exhaust fan in the car ceiling. | 8/20/2019 | ||
conversion | conversion | n/a | Obtain and display a current state operating certificate in the machine room | 8/20/2019 | ||
conversion | conversion | n/a | Replace the two 20 amp breakers tied together with a piece of copper wire with an approved device or replace the breaker with an two pole breaker. | 8/20/2019 | ||
conversion | conversion | n/a | Replace the broken arrow board in the jamb. | 8/20/2019 | ||
conversion | conversion | n/a | Repair the machine room door as it is to be self closing, self latching. | 8/20/2019 | ||
conversion | conversion | n/a | Replace the missing receptical cover in the pit. | 8/20/2019 | ||
conversion | conversion | n/a | Supply a non combustible holder with clear cover for the state operating certificate in the machine room | 8/20/2019 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean up the gunk from the pit floor. | 8/20/2019 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Replace the missing fire extinguisher in the machine room. | 11/15/2022 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Have the expired fire extinguisher re-certified. | 11/6/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove the stored materials and equipment from the elevator equipment room. | 11/6/2024 | ||
A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(4) | x | Re-pack the leaking jack seal. | 11/6/2024 | |
MO Minimum : Elevators | (I) - Pits | (I)1 | Clean up the oil from the pit floor. | 11/6/2024 |