Inspection
Inspection Details
Equipment ID
13040
13040
Inspection Date
5/28/2019
5/28/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
1b79411f-500d-4b4a-a7e1-911439e85272
1b79411f-500d-4b4a-a7e1-911439e85272
Location
Merchandise Mart Apartments
1000 WASHINGTON AVE, SAINT LOUIS, MO
1000 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Mermart LLC
911 WASHINGTON AVE STE 400, SAINT LOUIS, MO 63101-1208
911 WASHINGTON AVE STE 400, SAINT LOUIS, MO 63101-1208
Billing
Attn: Mermart LLC
1000 WASHINGTON AVE, SAINT LOUIS, MO 63101-1237
1000 WASHINGTON AVE, SAINT LOUIS, MO 63101-1237
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Repair inoperable emergency phone | 5/28/2019 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 4/29/2020 | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | Fire extinguisher needs to be serviced. | 8/10/2020 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 4/30/2021 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. | 6/17/2022 | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5c Receptacles | A duplex GFCI receptacle rated at not less than 15 A, 120 V shall be provided in each machine room and machinery space. | 11/7/2023 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 11/7/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | The signage for “In Case of Fire” is missing on a number of landings. Install signage that conforms to the building code this elevator was installed to meet. | 11/7/2023 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Remove all the non elevator related items from the elevator machine room. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide current year tested fire extinguisher in the elevator machine room. | |||
| A17.1-1996 : Elevators | 5.11 Plunger and Cylinder | 1206.5b(5) Oil Leakage Collection | Remove oil return lines going back to the tank. Provide each piston means to collect oil in the pit. |