Inspection
Inspection Details
Equipment ID
2703
2703
Inspection Date
5/21/2019
5/21/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joseph Blankenship
Joseph Blankenship
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
cb8f565d-b555-4eeb-99e5-8a8d9323365d
cb8f565d-b555-4eeb-99e5-8a8d9323365d
Location
School of Dentistry
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: UMKC- Parking Structure
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | need to have two working ligh fixtures in the car | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Repair pit light, it did not work. possible burnt out bulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Replace the emergency light battery, it is dead | 6/4/2020 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current copy of the state operating certificate in the machine room | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide access to the complete MCP in the machine room according to 8.6 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | bottom landing freight door hoistway access pull chain cover lock is broken and needs to be repaired | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | replace the emergency light battery, it is almost dead | 8/16/2021 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. the one in the room is from 2016 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | could not find the any of the oil record logs, logs are to be kept in the machine room for 5 years. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2017 | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace missing pull strap on level B hoistway door | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Water in the pit, unclogged floor drain in the pit | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light does not work no lightbulb in fixture, replace lightbulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Recovery pump in the pit needs to be replaced with a 5 gallon bucket per state memo 6 (8.6.5.5.2) |