Inspection
Inspection Details
Equipment ID
2683
2683
Inspection Date
5/15/2019
5/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joseph Blankenship
Joseph Blankenship
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
11
11
External ID
7853c20e-806c-46e6-8bc1-a5b7f681b69b
7853c20e-806c-46e6-8bc1-a5b7f681b69b
Location
Haag Hall
5120 ROCKHILL RD, KANSAS CITY, MO
Phone: (816) 235-1363
5120 ROCKHILL RD, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: UMKC- Parking Structure
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Replace emergency light battery, it is dead | 5/20/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell needs to be repaired/replaced; the striker works but doesn't ting the bell. | 8/16/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. The certificate in the machine room is from 2019 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | the machine room fire extinguisher inspection tag is from 2019, have the extinguisher inspected and tagged annually | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | the door restrictor did not work, replace the missing hook on the door restrictor and adjust the restrictor so it functions | 6/12/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | machine room fire extinguisher inspection tag is from 2019, have extinguisher inspected annually | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag is from 2019, have extinguisher inspected annually |