Inspection
Inspection Details
Equipment ID
15019
15019
Inspection Date
5/15/2019
5/15/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joseph Blankenship
Joseph Blankenship
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
5732f256-1c9e-4703-a91e-47bf6d0829ea
5732f256-1c9e-4703-a91e-47bf6d0829ea
Location
Oak Street Housing
5051 OAK ST, KANSAS CITY, MO
5051 OAK ST, KANSAS CITY, MO
Owner
Attn: UMKC- Parking Structure
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110
Phone: (000) 000-0000
Email: hickmanch@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.11.3.1.1(h) | Yes | No | adjust the door close force to below 30 lbs, the doors maxed out my gauge (2.13.4.2.3) | 6/16/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | repair and adjusted door restrictor, it is not working | 6/3/2024 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | replace first floor hoistway door astragal, it is no longer glued to the bottom half of the door | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | clean up the oil on the pit floor | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | repair machine room air conditioner so it works | |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Repair and adjust door restrictor, it is not working | 8/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil from the pit |