Inspection
Inspection Details
Equipment ID
3213
3213
Inspection Date
2/21/2018
2/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
21 Lbf
21 Lbf
External ID
Location
Drury Plaza Hotel
2 South 4th St, St. Louis, MO
Phone: (314) 231-3003
2 South 4th St, St. Louis, MO
Phone: (314) 231-3003
Owner
Drury Hotels
8315 Drury Industrial Pkwy, St. Louis, MO 63114
8315 Drury Industrial Pkwy, St. Louis, MO 63114
Billing
Attn: Drury Hotels
721 Emerson Rd, Suite 400, , MO 63141
721 Emerson Rd, Suite 400, , MO 63141
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair machine room lights | 6/20/2020 |
| conversion | conversion | n/a | No | No | Replace hoist (supension) rope within 30 days. | 6/20/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Cables are roughing and need replacing. Cables on are contract to be changed Jan 2019. | 1/16/2019 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace governor rope. 2.13.2.1 (a) | 6/10/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase 2 signage needs to be replaced inside of car. 6.1.2.(g)(1) No need to red tag or reinspect. | 6/20/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The lighting in the elevator machine room above the drive machine is not sufficient. The lighting shall not be less than (10) foot candles at the floor level. | 12/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car is worn off and unreadable. Replace signage as required. | 12/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 2/5/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room is not for storage. The unused air coolers and supply ducts shall be removed | 2/12/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | The smoke detectors in the elevator pits are covered with plastic preventing them from operating properly. The covers shall be removed and the detectors checked for proper operation. Re-inspection required | 2/12/2026 |