Inspection
Inspection Details
Equipment ID
19915
19915
Inspection Date
5/7/2019
5/7/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Michael Elder
Michael Elder
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
13
13
External ID
c013c759-e7c5-4ef3-8ef5-9118b1efb2f8
c013c759-e7c5-4ef3-8ef5-9118b1efb2f8
Location
Arrowhead Stadium
1 ARROWHEAD DR, KANSAS CITY, MO
1 ARROWHEAD DR, KANSAS CITY, MO
Owner
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
Billing
Attn: Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
1 ARROWHEAD DR, KANSAS CITY, MO 64129-1651
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Repair the hoistway access keyswitches on both the top and bottom landings | 7/18/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | the alcove for the governor and machine does not have adequate illumination, it shall be not less than 200 lux (19 foot-candles) at the floor level. measured around 3 foot-candles | 7/18/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | The alcove for the machine and governor needs more lights, the one light bulb that is in the alcove does not provide 19 foot candles of illumination at the floor | 7/18/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | The Maintenance Control Program On-Site documents are not in the machine room. | 7/18/2025 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency lights did not come on, alarm bell worked, replace the batteries, verify the battery charger is functioning. | 6/3/2022 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | light in the alcove for the machine space is burnt out, when it did work it did not provide the required illumination at the floor of 19 foot candles | 7/18/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/18/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. The one in the machine room is from 2017 | 7/18/2025 | ||
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | Emergency lights did not come on, repair emergency light system. | 5/23/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | need additional ligh fixture over the governor and machine, illumination to to code standards of 19 foot candles measured at the floor | 7/18/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/18/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/18/2025 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | emergency light battery is dead, replace emergency light battery | 11/14/2023 |