Inspection
Inspection Details
Equipment ID
7416
7416
Inspection Date
6/5/2019
6/5/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
28
28
External ID
3d42f511-02b6-4bd2-afed-bfcfde9a1e35
3d42f511-02b6-4bd2-afed-bfcfde9a1e35
Location
Sheraton Hotel
7730 BONHOMME AVE, CLAYTON, MO
7730 BONHOMME AVE, CLAYTON, MO
Owner
Attn: Aimbridge Hospitality
Aimbridge Hospitality
5851 Legacy Circle, Suite 400, Plano, TX 75024
Phone: (314) 863-0400
Email: Licensing@aimhosp.com
Aimbridge Hospitality
5851 Legacy Circle, Suite 400, Plano, TX 75024
Phone: (314) 863-0400
Email: Licensing@aimhosp.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Emergency exit shall be operable, remove temporary weights from top of hatch. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Pit sump pump hole is not covered. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | Counterweights are compressing buffer in pit when car is at top landing. Shorten ropes to provide minimum runby of 6" | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance records on site. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Emergency hatch shall be operable. Remove temporary weights from top of hatch. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be provided on site. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | No | No | Sump pump hole shall be covered. | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | Counterweights are compressing buffer in pit when car is at the top landing. Hoist ropes need to be shortened to get minimum runby of 6". | 4/14/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance control program in the machine room | 4/14/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Test incomplete. Car top still needs to be inspected | 10/12/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing on emergency power. | 8/9/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing. | 8/9/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)6 | Yes | No | Re-install buffer switches on car and counterweights. | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil off of pit floor. | 10/14/2025 |