Inspection
Inspection Details
Equipment ID
15038
15038
Inspection Date
3/26/2019
3/26/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
500
500
Slide
2'
2'
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
a8cab9b1-96a2-41c0-895e-859eabd55b78
a8cab9b1-96a2-41c0-895e-859eabd55b78
Location
Kauffman Stadium
103 ROYAL WAY, KANSAS CITY, MO
103 ROYAL WAY, KANSAS CITY, MO
Owner
Attn: Kauffman Stadium
Kauffman Stadium
1 ROYAL WAY, KANSAS CITY, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Kauffman Stadium
1 ROYAL WAY, KANSAS CITY, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Billing
Attn: Kauffman Stadium
Kauffman Stadium
1 ROYAL WAY, KANSAS CITY, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Kauffman Stadium
1 ROYAL WAY, KANSAS CITY, MO 64129
Phone: (816) 504-4242
Email: Todd.burrow@royals.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.29 - Car and counterweight safeties | Table 2.17.3 | Yes | Yes | according to table maximum stopping distance is 16 inches, measured 24 inches. make adjustments and schedule reinspection | 7/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the State Operating Certificate in the machine room | 3/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Post monthly fire service test log in the machine room | 3/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Post instructions for viewing on-site the records for the Maintenance Control Program (MCP) | 3/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.2 - Stop switches | 8.11.2.1.1(b) (Re-Inspection) | No | No | replace broken stop switch on the auxiliary car operating panel | 4/25/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 3/15/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 3/15/2026 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | No | No | Replace burnt out light in the level 2 lobby. The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 100 lx (10 fc). | 3/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone not working, call could not be completed as dialed | 4/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | a new copy of the state operating certificate is to be posted in the machine room every year | 3/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | a monthly fire service test log is to be available in the machine room | 3/15/2026 |