Inspection
Inspection Details
Equipment ID
21486
21486
Inspection Date
5/22/2019
5/22/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
1650
1650
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
e34a64c2-6a30-4dda-96a5-c779ea362837
e34a64c2-6a30-4dda-96a5-c779ea362837
Location
Henry Elementary School
1220 N 10TH ST, SAINT LOUIS, MO
1220 N 10TH ST, SAINT LOUIS, MO
Owner
Attn: UNK
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
Billing
Attn: Cindy Williams
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: cindy@advancedelevator-stl.com
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: cindy@advancedelevator-stl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall not be used for the storage of non-elevator related materials. | 2/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | The door closing force exceeds the 30 lbs. limit. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 6/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Battery lowering did not work, Re-inspection required | 1/6/2023 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV shall be tested. Re-inspection required | 1/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 8.11.3.2.5 Pressure Switch (Re-Inspection) | Yes | No | Repair or replace inoperative low pressure switch. | 5/13/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 8.11.3.2.5 Pressure Switch (Re-Inspection) | Yes | No | Repair or replace inoperative low pressure switch. | 5/13/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 8.11.3.2.5 Pressure Switch (Re-Inspection) | Yes | No | Repair or replace inoperative low pressure switch. | 5/13/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | Yes | Repair or replace inoperative pressure switch. Pressure switch has not operated since 5/21/24. Repair and reinspection required. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time, proper equipment was not available to test the car safeties. The car safeties shall be tested and the battery lowering device tested before a full inspection can be completed. Reinspection is required. |