ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.3 - Top-of-car operating device
|
8.11.2.1.3(c)
|
No
|
No
|
Car top inspection switch is broken and shall be repaired or replaced.
|
10/18/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
2.16
|
No
|
No
|
A capacity plate is missing inside the car. Plate shall state the capacity is 1400 lbs.
|
10/18/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.2.1.1(e) Car Lighting
|
No
|
No
|
In cab emergency light and alarm bell shall work.
|
10/18/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
10/20/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational with 110v source removed.
|
8/18/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
5/25/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone is working, establishes 2-way communication, but the answering agent cannot provide site location information.
|
2/9/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone shall work.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Operating certificate required in the machine room.
|
|