Inspection
Inspection Details
Equipment ID
21917
21917
Inspection Date
6/4/2019
6/4/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
2"
2"
Governor Rope Pull
25/120
25/120
Door Closing Force
20
20
External ID
0143eb9c-a9d7-4770-892c-2132ad7b389e
0143eb9c-a9d7-4770-892c-2132ad7b389e
Location
Laclede Lofts
3965 LACLEDE AVE, SAINT LOUIS, MO
3965 LACLEDE AVE, SAINT LOUIS, MO
Owner
Attn: Jewel of the Plaza LLC
Jewel of the Plaza LLC
393 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Jewel of the Plaza LLC
393 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Billing
Attn: Red Brick Management
Red Brick Management
393 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: steve@redbrickstl.com
Red Brick Management
393 N EUCLID AVE, SAINT LOUIS, MO 63108
Phone: (000) 000-0000
Email: steve@redbrickstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Inspection not completed because mechanic couldn't access the machine room. All items in the machine room shall be checked for code compliance. | 4/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Door pressure, light/bell/phone, SOS still need to be tested. | 4/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire tabs are missing on hoistway doors. | 4/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Replace any missing fire tabs on hoistway doors. | 4/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove excess debris from pit. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Remove excess debris. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Replace any missing fire tabs on hoistway doors. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Maintenance visits, inspections, and fire service testing is not being properly documented. | 6/10/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire tabs missing on hoistway doors. (3rd Notice) | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 2.21 | Yes | No | Insert missing guiding members from top left counterweight guide. | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it. | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided in the machine room. | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current ABC fire extinguisher shall be provided in the machine room. | 10/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided in the machine room. Not verified during reinspection. Owner to self-certify. | 4/10/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current ABC fire extinguisher shall be provided in the machine room. Not verified during reinspection. Owner to self-certify. | 4/10/2026 |