Inspection
Inspection Details
Equipment ID
2886
2886
Inspection Date
6/11/2019
6/11/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Michael Gallaher
Michael Gallaher
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
External ID
6dd6f4f1-f476-44bb-8791-e7a622ff898b
6dd6f4f1-f476-44bb-8791-e7a622ff898b
Location
Gasconade Pump Station
4105 S 1ST ST, SAINT LOUIS, MO
4105 S 1ST ST, SAINT LOUIS, MO
Owner
Metropolitan Sewer District STL
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Billing
Attn: Metropolitan Sewer District
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency phone not working | 10/15/2020 |
| conversion | conversion | n/a | No | No | Post MO operating certificate in machine room | 10/15/2020 |
| conversion | conversion | n/a | No | No | Need maintenance control program | 10/15/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Provide protection for cab lighting. | 10/15/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone. | 4/30/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate in machine room. | 10/15/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | No | No | Secure cab panel to platform. | 10/15/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | Replace missing gate latches at 1st and 2nd landings. | 10/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair gate restrictor for proper operation. | 10/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency phone line must call and be received by a 24 hour service line. | 10/16/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks. | 10/16/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | The hoistway gate must be at least 7 feet high at each landing sill. | 10/16/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The Current operating certificate shall be posted in the machine room in a non combustible frame | 10/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements | 10/15/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Gates must have interlocks and be at least 7" high at each landing. Red tagged elevator. |