Inspection
Inspection Details
Equipment ID
18322
18322
Inspection Date
6/24/2019
6/24/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
William Bracht
William Bracht
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
623f8f17-0f52-4d0f-b5aa-41b16d87f995
623f8f17-0f52-4d0f-b5aa-41b16d87f995
Location
De Paul Parking Garage
12303 DE PAUL DR, BRIDGETON, MO
12303 DE PAUL DR, BRIDGETON, MO
Owner
Attn: Leslie Thornburg
De Paul Health Center
12303 DE PAUL DR, BRIDGETON, MO 63044
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
De Paul Health Center
12303 DE PAUL DR, BRIDGETON, MO 63044
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The ventilation fan in the machine room needs to be repaired to provide proper operation temperature for the elevator controller. | 2/7/0202 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 2/7/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 2/7/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 8/17/2020 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | The handrail in the elevator car has been removed and needs to be reinstalled to comply with ADA requirements. | 12/21/2022 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | 12/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. | 8/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A door retainer gib is missing on the 3rd floor, reinstall missing gib. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A door retainer gib is missing on the 3rd floor, reinstall missing gib. |