Inspection
Inspection Details
Equipment ID
12244
12244
Inspection Date
6/10/2019
6/10/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
6115b2ef-a148-4318-acdd-2c276df6ab36
6115b2ef-a148-4318-acdd-2c276df6ab36
Location
St. Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
Owner
Attn: Leslie Thornburg
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Car and counterweight buffers need to be drained of water and refilled. | 11/11/2019 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room needs to be a minimum of 10 ft candles to the floor | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 5/13/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that either the device is not hooked up to a back-up power device or the back-up power device as failed. Repair for proper operation. Reinspection required. | 5/13/2025 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | The hoist rope deflector sheave, at the top of the hoistway, has never been secured properly on the supporting I-beam. Without this sheave being secured, upon striking the counterweight buffer the sheave could move causing severe damage to the elevator which has happened in the past at other locations. Properly secure the sheave to the I-Beam. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | Elevator car door restrictor does not work, needs repaired. Re-inspection required | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Need to clean trash from elevator pit | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to test elevator for operation on emergency power. Re-inspection required | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Re-inspection is required |