Inspection
Inspection Details
Equipment ID
11723
11723
Inspection Date
6/11/2019
6/11/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
8cd00ec0-f475-4174-8e88-8c1574b92698
8cd00ec0-f475-4174-8e88-8c1574b92698
Location
St. Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
Owner
Attn: Leslie Thornburg
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Cab flooring is loose, protruding above car sill causing trip hazard. | 10/13/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair cab floor at opening, it is a tripping hazard | 10/13/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No ventilation in machine room. Controllers are in extreme heat, over manufacturers recommendations. 101.5b | 10/13/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | Yes | Yes | The elevator safety governor was found to be worn to a degree that the activation would not set with any sort of consistency. Repair or replacement of the governor is required and a re-inspection shall be performed before the elevator can be returned to service. | 11/8/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean dirt, grease and debris from elevator car top | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor needs repaired. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test phase I and II fire service key. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase II fire service operating instructions are missing inside of elevator cab, need to install correct signage | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th and 6th floor hoistway doors, needs repaired. | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | 5/6/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase II fire service operating instructions are missing inside the elevator cab, need to install correct signage | 5/6/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)4 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired | 5/6/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)4 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |