Inspection
Inspection Details
Equipment ID
7153
7153
Inspection Date
3/1/2018
3/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
24lbs
24lbs
External ID
Location
HoteLumiere
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Pinnacle Entertainment
3800 Howard Huges Parkway, Las Vegas, NV 89109
3800 Howard Huges Parkway, Las Vegas, NV 89109
Billing
Attn: HoteLumiere
901 North 1st St, , MO 63102
901 North 1st St, , MO 63102
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Machine room lights out, repair | 2/26/2024 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine leaking oil in hoistway. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lights need repair. 10 ft candle minimum | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated current operating certificate in machine room. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Emergency light lens needs to be replaced. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Machine room lights shall be 10 ft candles. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency light & alarm bell not working. Re-inspection required | 12/20/2022 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in the machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Machine leaks oil onto floor, into hoistway, need to repair same | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | |||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Doors do not open when recalled in Fire Fighters Emergency Service, runs between 1 and 2 without opening doors, even using door button. Red-tagged, Re-inspection required | 2/13/2024 |
MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Lighting in machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Machine leaks oil onto floor, into hoistway, needs repaired | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | x | Inside of car call buttons are inoperable and shall be repaired to ensure safety for all elevator use. | 9/18/2024 | |
A17.1-2016 : Elevators | 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) | 8.6.11.1 Firefighters’ Emergency Operation | x | x | Phase 1 recall inoperable and shall be repaired to meet the correct fire service requirements. | 9/18/2024 |