Inspection
Inspection Details
Equipment ID
7154
7154
Inspection Date
3/1/2018
3/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
21 lbs
21 lbs
External ID
Location
HoteLumiere
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
901 North 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Pinnacle Entertainment
3800 Howard Huges Parkway, Las Vegas, NV 89109
3800 Howard Huges Parkway, Las Vegas, NV 89109
Billing
Attn: HoteLumiere
901 North 1st St, , MO 63102
901 North 1st St, , MO 63102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room lights out, repair. | 1/28/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room door should be self closing and locking. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating cert in the machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 4/19/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Hoist ropes need to be replaced, Red Tagged, needs RE-inspection | 12/20/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light & alarm bell not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit stop switch shall be easily visible from bottom floor, pit switch is painted brown and not visible | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing & self locking | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable has breaks, replace same | 11/26/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit stop switch shall be easily visible from bottom floor. Pit stop switch is painted brown, not easily visible. | 11/26/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | Pit stop switch shall be easily visible from bottom floor. Pit switch is painted brown and not visible | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and self locking | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable has breaks. Replace | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Pick up roller missing on floor 8 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Gib missing on floors 8, 4, 3 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency Bell not working |