Inspection
Inspection Details
Equipment ID
12805
12805
Inspection Date
6/4/2019
6/4/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Douglas Gildehaus
Douglas Gildehaus
Relief Valve Pressure
680
680
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
1fa7d259-4fc1-4e8b-8837-5f76f846a274
1fa7d259-4fc1-4e8b-8837-5f76f846a274
Location
98 Building
1 UNITED DR # B-4, FENTON, MO
1 UNITED DR # B-4, FENTON, MO
Owner
Attn: UniGroup
Uni Group Inc
1 PREMIER DR, FENTON, MO 63026
Phone: (000) 000-0000
Email: tom_fitzgerald@unigroup.com
Uni Group Inc
1 PREMIER DR, FENTON, MO 63026
Phone: (000) 000-0000
Email: tom_fitzgerald@unigroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A monthly record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 7/14/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Hydraulic fluid collection container in the pit shall not exceed 5 gallon capacity. | 7/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans, shall not exceed 5 gal before removal, shall be covered, and shall not be permitted to overflow. | 7/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Per the State of Missouri AHJ: "The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals", and "machine rooms cannot be used as containment areas". | 7/22/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP fire service testing must be properly documented monthly. | 9/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Pit scavenger pump shall be removed. Drain tube to be routed to a measurable container in pit. | 9/1/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove excess debris. | 9/1/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | No answer on emergency phone. Take corrective action and re-test. | 7/1/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Clean the pit. | 7/3/2024 |