Inspection
Inspection Details
Equipment ID
16972
16972
Inspection Date
6/5/2019
6/5/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Rick Buttice
Rick Buttice
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
1169280c-02e9-424b-aab2-9eebb85468db
1169280c-02e9-424b-aab2-9eebb85468db
Location
Old Hickory Golf Club
1 DYE CLUB DR, SAINT PETERS, MO
1 DYE CLUB DR, SAINT PETERS, MO
Owner
Old Hickory Golf Club
1 DYE CLUB DR, SAINT PETERS, MO 63304-1104
1 DYE CLUB DR, SAINT PETERS, MO 63304-1104
Billing
Attn: Old Hickory Golf Club
1 DYE CLUB DR, SAINT PETERS, MO 63304-1104
1 DYE CLUB DR, SAINT PETERS, MO 63304-1104
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 6/5/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Car emergency lighting shall work. | 7/16/2019 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 7/27/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Phase 2 firefighters operation instructions shall be legible. | 7/27/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/31/2020 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | No | No | The car, riding directional indicator lantern is missing, resulting in exposed wiring. The lantern shall be replaced and wires shall be enclosed. | 7/27/2020 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Holes in the machine room wireway shall be covered. | 7/27/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 6/28/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/28/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean and dry. | 6/28/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate is required in the machine room. | 6/28/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 4/3/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean and dry. Water shall be removed from pit floor. | 4/3/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean and dry. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the machine room. |