Inspection
Inspection Details
Equipment ID
13817
13817
Inspection Date
6/3/2019
6/3/2019
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Edward Bauer
Edward Bauer
Relief Valve Pressure
525
525
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
676cc4ab-2491-4653-8989-030b914cc82d
676cc4ab-2491-4653-8989-030b914cc82d
Location
St. Francois County Courthouse
1 N WASHINGTON ST, FARMINGTON, MO
1 N WASHINGTON ST, FARMINGTON, MO
Owner
Attn: St. Francois County Courthouse
St. Francois County Courthouse
1 N WASHINGTON ST, FARMINGTON, MO 63640
Phone: (573) 631-8039
Email: bbriley@sfcgov.org
St. Francois County Courthouse
1 N WASHINGTON ST, FARMINGTON, MO 63640
Phone: (573) 631-8039
Email: bbriley@sfcgov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 1) Maintenance records shall document compliance with 8.6 of the Code and shall include records on the all activities. | 7/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 1) The following documents specified in 8.6.1.2.2(a), (b), and (c) shall be written and permanently kept on-site in the machine room, machinery space, control room, control space in hard copy for each unit for elevator personnel. (b) Procedures for inspections and tests are not on site. Ref: 8.6.1.2.2 | 7/1/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | 2) Installation of electrical equipment and wiring shall conform to NFPA 70. Traveling cables shall be supported as per article 620.41. Ref: 2.8.2.1 | 7/1/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | 3) Installation of electrical equipment and wiring shall conform to NFPA 70. Traveling cables shall be ran in a raceway, 6 ft. from first point of support on the hoistway wall as per article 620.44(b). Ref: 2.8.2.1 | 7/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Incomplete maintenance control program procedures for inspections and test are not on-site. | 4/20/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV five (5) year test due at next inspection. | 4/20/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current operating certificate. | 4/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light failed to operate when 110 disconnected. | 7/29/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Standing water in pit. Pit shall be kept clean and dry. | 8/27/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate during test. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light failed when 110 disconnected. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell failed. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Basement level lobby flooring threshold at elevator exit causing a tripping hazard. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Basement level lobby flooring threshold at elevator exit causing a tripping hazard. |