Inspection
Inspection Details
Equipment ID
9712
9712
Inspection Date
6/14/2017
6/14/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
R-20 F-18
R-20 F-18
External ID
Location
Grand Regency
175 Golf View Dr, Branson, MO
Phone: (417) 336-6288
175 Golf View Dr, Branson, MO
Phone: (417) 336-6288
Owner
Inderfit Igrewal
245 Jess Jo Parkway, Branson, MO 65616
245 Jess Jo Parkway, Branson, MO 65616
Billing
Attn: Colonnade
245 Jess Jo Parkway, , MO 65616
245 Jess Jo Parkway, , MO 65616
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Front hoistway door entrance sill support / gaurd requires to be repaired or replaced.(due to water rusting) | 9/22/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phone Failed | 9/22/2018 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Proper locking device on machine room door | 5/3/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone Failed | 5/29/2019 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5c Receptacles | No | No | Machine Room Light not working | 7/11/2019 |
| A17.1-2016 : Elevators | 10.1 - Machinery space access, lighting, receptacle, and condition | 8.11.4.1(s) | No | No | Unauthorize material stored in machine room | 8/14/2020 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Sump pump not working accumalation of water | 8/14/2020 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Must make key position labeling On/Off/Reset Readable. | 9/30/2021 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Must make emergency Light operable. 1.6 | 11/14/2022 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Must test and document Fire service Monthly. (Currently only documented every 4 months) | 7/1/2022 |