Inspection
Inspection Details
Equipment ID
18210
18210
Inspection Date
6/4/2019
6/4/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Leo
David Leo
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18
18
External ID
66db8161-7d8a-4132-aec8-e215989cbbdd
66db8161-7d8a-4132-aec8-e215989cbbdd
Location
Cupples Station Building #1
1000 CLARK AVE, SAINT LOUIS, MO
1000 CLARK AVE, SAINT LOUIS, MO
Owner
Cupples Station Bldg
1000 CLARK AVE, SAINT LOUIS, MO 63102-1112
1000 CLARK AVE, SAINT LOUIS, MO 63102-1112
Billing
Attn: Cassidy Turley
575 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141-5813
575 MARYVILLE CENTRE DR, SAINT LOUIS, MO 63141-5813
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Install machine area lighting to provide 19 foot candles of illumination with the switch adjacent to & accessible from the top floor door | 10/9/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Provide 19 foot candles of illumination measured at the floor in the control space | 10/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unintended test procedures do not appear proper for this controller. Re-inspection required | 9/1/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Need to install machine area lighting to provide 19 foot candles of illumination with the switch adjacent to & accessible from the top floor door. | 10/9/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Need to provide 19 foot candles of illumination measured at the floor in the control space | 10/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unintended test procedures do not appear proper for this controller, still unable to perform unintended movement testing. Re-inspection required | 9/5/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Need to install machine area lighting to provide 19 ft candles of illumination with the switch adjacent to and accessible from the top floor door | 10/9/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Provide 19 foot candles of illumination measured at the floor in the control space | 10/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | I.1 - The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. | 10/9/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate shall be displayed in elevator machine room. | 10/9/2025 |