Inspection
Inspection Details
Equipment ID
12664
12664
Inspection Date
6/15/2017
6/15/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
12664
12664
Location
West County Center
44 West County Center, Des Peres, MO
Phone: (314) 288-2020
44 West County Center, Des Peres, MO
Phone: (314) 288-2020
Owner
CBL Properties
2030 Hamilton Place Blvd., Ste 500, Chattanooga, TN 37421
2030 Hamilton Place Blvd., Ste 500, Chattanooga, TN 37421
Billing
Attn: West County Center
80 West County Center Dr, , MO 63131
80 West County Center Dr, , MO 63131
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Clean down truss | 10/10/2019 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Left side handrail needs to be replaced. It has cracks in it. | 10/10/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 1206.6 | No | No | Entire truss needs to be cleaned out. | 10/10/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.7 | No | No | Replace broken step teeth as needed. | 10/10/2019 |
| A17.1-1996 : Escalators | 8.12 - Steps, step chains, and trusses | 802.8 | No | Yes | Step chain clearances do not meet requirements. | 10/10/2019 |
| A17.1-1996 : Escalators | 8.4 - Drive machine and brake | 804 | Yes | Yes | Brake does not meet minimum brake torque. | 10/10/2019 |
| A17.1-1996 : Escalators | 7.15 - Balustrades | 802.3 | No | No | Bottom deck guards are wrong height and distance from handrail. | 10/10/2019 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.4 | No | No | Replace right handrail due to excessive wear. | 10/25/2019 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Need to perform clean down of unit | 3/13/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.7 Rollers, Tracks, and Chains | Yes | Yes | Unit has stress crack in lower end step track, Red-tagged, Re-inspection required | 3/13/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Two steps have broken nose pieces, replace same | 3/13/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | Yes | Yes | Left handrail has cracks / pinch points, replace same. Red-tagged, Re-inspection required | 3/13/2026 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform step indexing to complete inspection. Re-inspection required | 3/13/2026 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform testing of all comb impact devices to complete inspection. Re-inspection required | 3/13/2026 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | Yes | No | Testing of the right side failed. |