Inspection
Inspection Details
Equipment ID
485
485
Inspection Date
7/2/2019
7/2/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Thomas Kitzinger
Thomas Kitzinger
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
30
30
External ID
8ba890fd-57b2-43fd-9327-2cd41a6097ff
8ba890fd-57b2-43fd-9327-2cd41a6097ff
Location
Central High School
116 REBEL DR, PARK HILLS, MO
116 REBEL DR, PARK HILLS, MO
Owner
Attn: Central R-3 School District
Central R-3 School District
200 HIGH ST, PARK HILLS, MO 63601
Phone: (000) 000-0000
Email: billing@centralr3.org
Central R-3 School District
200 HIGH ST, PARK HILLS, MO 63601
Phone: (000) 000-0000
Email: billing@centralr3.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | 2nd floor hoistway door needs pick-up roller. | 9/19/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Lower photo eye (door reopening device) shall work. | 9/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide pit bucket | 3/21/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency battery lowering unit not working | 7/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Missing hoist way door rollers at top floor | 7/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide pit bucket. | 3/21/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 3/21/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery backup lowering unit is not working properly. | 10/28/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work, no power. | 10/28/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 10/7/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work properly. | 2/6/2025 |