Inspection
Inspection Details
Equipment ID
22063
22063
Inspection Date
6/20/2019
6/20/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Herbert Neulist
Herbert Neulist
Mechanic Name
Douglas Gildehaus
Douglas Gildehaus
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
62863ea9-7be8-474a-a2d5-6969d5e0d03b
62863ea9-7be8-474a-a2d5-6969d5e0d03b
Location
Victorian Gardens
15 HILLTOP VILLAGE CENTER DR, EUREKA, MO
15 HILLTOP VILLAGE CENTER DR, EUREKA, MO
Owner
Victorian Gardens
1015 SPRINGFIELD RD, OWENSVILLE, MO 65066-2354
1015 SPRINGFIELD RD, OWENSVILLE, MO 65066-2354
Billing
Attn: Victorian Gardens
3808 HIGHWAY 19, OWENSVILLE, MO 65066-3003
3808 HIGHWAY 19, OWENSVILLE, MO 65066-3003
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit needs to be cleaned | 6/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | Oil hose on left cylinder needs to be reattached for proper measurements of oil loss | 6/20/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Oil hose on left cylinder needs to be re-attached for proper measurement of oil loss | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 7/3/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit stopped operating during testing. Need to perform testing of fire service and door closing force to complete inspection. Re-inspection required | 7/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean oil, water & debris from elevator pit | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 6/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Oil hose on left cylinder needs to be re-attached for proper measurement of oil loss. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work. Re-inspection required |