Inspection
Inspection Details
Equipment ID
12255
12255
Inspection Date
6/18/2019
6/18/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
18
18
Governor Rope Pull
100/665
100/665
Door Closing Force
18
18
External ID
653a7bd5-0e67-4eaf-9874-badf46b552f8
653a7bd5-0e67-4eaf-9874-badf46b552f8
Location
St. Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
3635 VISTA AVE AT GRAND, ST. LOUIS, MO
Owner
Attn: Leslie Thornburg
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
SSM Saint Louis University Hospital
3635 VISTA AVE AT GRAND, ST. LOUIS, MO 63110
Phone: (314) 989-6134
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Counterweight strikes buffer with car at top floor, has no runby. Hoist ropes need to be shortened. Reinspect within 90 days. | 10/14/2021 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | No | No | Counterweight landing on buffers at top floor, hoist ropes need to be shortened. Re-inspect in 90 days 1206.8 | 12/28/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 11/21/2025 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | When the full load car safety test was performed, the car slide was 42". The maximum allowed is 28". Repair or replace car safeties to get proper slide distance. Re-inspection within 30 days required | 7/2/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 7/2/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 7/2/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 11/21/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 11/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 11/21/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 3/25/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 3/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 3/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |