Inspection
Inspection Details
Equipment ID
15341
15341
Inspection Date
6/26/2019
6/26/2019
Inspection Type
Initial Inspection
Initial Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
John Thrasher
John Thrasher
Relief Valve Pressure
Slide
20.25
20.25
Governor Rope Pull
130/620
130/620
Door Closing Force
18
18
External ID
d8373044-ffb6-48df-af85-dd4b41b3fb94
d8373044-ffb6-48df-af85-dd4b41b3fb94
Location
Windows On Washington-IBCI Bldg
1509 WASHINGTON AVE, SAINT LOUIS, MO
1509 WASHINGTON AVE, SAINT LOUIS, MO
Owner
Attn: Window On Washington-IBCI Bldg
IBC Investors LLC
PO BOX 5005, CAHOKIA, IL 62206-5005
IBC Investors LLC
PO BOX 5005, CAHOKIA, IL 62206-5005
Billing
Attn: IBC Investors LLC
Donny Choate
189 AMERICAN GRAIN ST, CAHOKIA, IL 62206-2938
Donny Choate
189 AMERICAN GRAIN ST, CAHOKIA, IL 62206-2938
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.12 | Yes | No | Remote governor trip not functioning. | 11/30/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 9/10/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 testing of the car safeties. Record slide. Check rails for dressing. | 9/10/2024 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed several bottom door guides (on different floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2 through 2.27.8 Firefighter Service | Yes | Yes | On Phase II operations, door close function not working. Car removed from service. | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 4/7/2026 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 safety test, record slide. | 4/7/2026 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed bottom door guides ( on several floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone in car not working. | 5/5/2026 |