Inspection
Inspection Details
Equipment ID
2755
2755
Inspection Date
2/21/2018
2/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sheila Swett
Sheila Swett
Mechanic Name
Relief Valve Pressure
Slide
22
22
Governor Rope Pull
200/750
200/750
Door Closing Force
18
18
External ID
29
29
Location
McMillan Hospital
517 S Euclid Ave, St. Louis, MO
Phone: (314) 362-2907
517 S Euclid Ave, St. Louis, MO
Phone: (314) 362-2907
Owner
WUSM
660 S, Euclid, St. Louis, MO 63110
660 S, Euclid, St. Louis, MO 63110
Billing
Attn: WUSM
660 S, Euclid, , MO 63110
660 S, Euclid, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Door restrictor not working. | 5/11/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | No | No | Observed car emergency lighting not working. | 3/3/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | No | No | Observed in-car alarm not working. | 3/3/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Emergency power is existing but was not tested. | 2/15/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Car emergency lighting not working properly - bulb out. | 2/15/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Observed alarm bell not working when 110V removed. | 2/15/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power is existing but was not tested. | 3/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lighting missing bulb and turns off and on when phone is activated. | 3/23/2021 |
| A17.1-2016 : Elevators | 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.11.2.1.3(mm) | No | No | Seismic switch (ring and string) not working. | 5/19/2022 |
| A17.1-2016 : Elevators | 3.23 - Suspension Means | 8.11.2.1.3(cc) | Yes | No | Suspension rope undersized. | 6/5/2023 |
| A17.1-2016 : Elevators | 1.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.11.2.1.1(y) | No | No | Seismic failed |