Inspection
Inspection Details
Equipment ID
15075
15075
Inspection Date
7/8/2019
7/8/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Justin Kennedy
Justin Kennedy
Relief Valve Pressure
590
590
Slide
Governor Rope Pull
Door Closing Force
16/18
16/18
External ID
1e2fb60b-32a9-4c7c-8cb4-48f16e7f9f43
1e2fb60b-32a9-4c7c-8cb4-48f16e7f9f43
Location
East Hills Library
502 N WOODBINE RD, SAINT JOSEPH, MO
502 N WOODBINE RD, SAINT JOSEPH, MO
Owner
Attn: St. Joseph Public Library
St. Joseph Public Library
927 FELIX ST, SAINT JOSEPH, MO 64501
Phone: (000) 000-0000
Email: mrevels@sjpl.lib.mo.us
St. Joseph Public Library
927 FELIX ST, SAINT JOSEPH, MO 64501
Phone: (000) 000-0000
Email: mrevels@sjpl.lib.mo.us
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.12 - Pipes, wiring, and ducts | 1001.2(c)(18) | No | No | Exposed 110 volt wiring on top of elevator needs to be in metal raceway | 8/22/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 7/17/2019 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 1/12/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Provide firefighters service key inside machine room, or on site. | 9/22/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | Doors do not open during firefighters phase 2 operation. 14 days allowed to fix this issue or elevator will be red tagged. | 1/12/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Keep monthly log of firefighters operation testing in machine room | 9/22/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Machine room door needs to be self-closing and self-locking. | 9/22/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 6/14/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or disconnect. "A17.1 1996" | 6/18/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Install code data plate "A17.1 1996" | 6/18/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 6/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Update the machine room fire extingusher. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service does not overide security. |