Inspection
Inspection Details
Equipment ID
19761
19761
Inspection Date
7/12/2019
7/12/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
UNK
UNK
Governor Rope Pull
120/980
120/980
Door Closing Force
28
28
External ID
6f47b03a-f355-49fa-a135-c18f7e82c564
6f47b03a-f355-49fa-a135-c18f7e82c564
Location
Bank of Washington
200 W MAIN ST, WASHINGTON, MO
200 W MAIN ST, WASHINGTON, MO
Owner
Bank of Washington
PO BOX 377, WASHINGTON, MO 63090-0377
PO BOX 377, WASHINGTON, MO 63090-0377
Billing
Attn: Bank of Washington
PO BOX 377, WASHINGTON, MO 63090-0377
PO BOX 377, WASHINGTON, MO 63090-0377
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.6.1.6.2 | Yes | No | Governor sheave is worn down and needs to be replaced. Pull through is way too tight. Need to set safeties and spin governor on reinspection within 60 days. | 10/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | Hoisting belts are rouged with steel strands poked through the belt. Belts shall be repaired/replaced. Maximum of 60 days to correct issue or unit will need to be red tagged out of service. | 5/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service must be tested and documented monthly. No Logs for 2022 - 2025. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service must be tested and documented monthly. No Logs for 2022 - 2025. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. No MCP, repair/PM/Callback logs for 2022 - 2025. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |