Inspection
Inspection Details
Equipment ID
22202
22202
Inspection Date
6/14/2019
6/14/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
TBD
TBD
Door Closing Force
TBD
TBD
External ID
5ce73884-b056-435d-be3d-508323632ebb
5ce73884-b056-435d-be3d-508323632ebb
Location
The Fountains at West County Assisted Living
15826 CLAYTON RD, ELLISVILLE, MO
Phone: (000) 000-0000
15826 CLAYTON RD, ELLISVILLE, MO
Phone: (000) 000-0000
Owner
Attn: The Fountains of Ellisville
The Fountains of Ellisville
15826 Clayton Road, Ballwin, MO 63011
Phone: (636) 220-1665
Email: sues@fountainsofwestcounty.com
The Fountains of Ellisville
15826 Clayton Road, Ballwin, MO 63011
Phone: (636) 220-1665
Email: sues@fountainsofwestcounty.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Could not test car over speed Governor due to door close button not working. | 8/24/2018 |
| conversion | conversion | n/a | No | No | Door Close Button does not work and need repair. | 6/22/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide a code compliant fire extinguisher near 4th floor elevator lobby entrance. | 10/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Provide category 5 generator test. | 9/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 8.11.2.1.4(l) | No | No | Provide testing of generator selector switch. | 10/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept clean. | 10/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | No | No | A fire service testing log shall be kept on-site. | 10/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Phase 1 & Phase 2 fire service operation shall be tested. | 9/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 8.11.2.1.1(h) | Yes | No | The door closing force shall be tested and the results recorded. | 9/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.1.2(bb) | Yes | No | Provide testing of car governor and record the electrical tripping and jaw speeds. | 9/12/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.26 - Broken rope, chain, or tape switch | 2.26.2.6 | Yes | Yes | The broken suspension member (belt) switches (there are 2) shall each stop the car independently. Note: Presently, both switches have to be tripped to stop the car. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/19/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/6/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust up-trust/doors for proper clearance to door hanger track, but not exceeding door to sill clearance allowance. (Multiple floors) | 9/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures. Fire service log to be recorded monthly. Note: Basic MCP is present but none of the required logs for 2021, 2022, and 2023. | 9/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work, with and without main power, and give proper location. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. | 1/3/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | 2-way communication device shall work, with and without main power, and give proper location. Note: Violation originally cited 9/26/23 and still not corrected. Elevator red tagged. | 5/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | Yes | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. Note: Violation originally cited 9/26/23 and still not corrected. Elevator red tagged. | 5/2/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Annual & Category 5 testing items that still need to be completed: unintended motion in up and down directions and slide to complete 5-year testing. | 5/2/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Door close button is broken and shall be replaced. | 9/23/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | The governor rope shall be shortened or other corrective action shall be taken to allow proper tension device clearance. | 3/30/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Annual & Category 5 testing items that still need to be completed: unintended motion in up and down directions and slide to complete 5-year testing. | 3/30/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. |