Inspection
Inspection Details
Equipment ID
16253
16253
Inspection Date
6/25/2019
6/25/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
160b1a77-d977-4e0c-b0a6-24e15067caf9
160b1a77-d977-4e0c-b0a6-24e15067caf9
Location
Country Inn & Suites- St. Charles
1190 S MAIN ST, SAINT CHARLES, MO
1190 S MAIN ST, SAINT CHARLES, MO
Owner
Attn: Country Inn & Suites- St. Charles
Waterworks Hotel Development Group
423 JACKSON ST, SAINT CHARLES, MO 63301
Phone: (636) 724-5555
Email: tgreeno@kinseth.com
Waterworks Hotel Development Group
423 JACKSON ST, SAINT CHARLES, MO 63301
Phone: (636) 724-5555
Email: tgreeno@kinseth.com
Billing
Attn: Country Inn & Suites- St. Charles
Country Inn & Suites- St. Charles
1190 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (636) 724-5555
Email: tgreeno@kinseth.com
Country Inn & Suites- St. Charles
1190 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (636) 724-5555
Email: tgreeno@kinseth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/2/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/2/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.1.7 | Yes | No | 8.6.1.7.5 - The auxiliary power lowering operation shall be functional. | 10/18/2021 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | No | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. | 12/2/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 12/2/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/2/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The auxiliary power lowering operation shall be functional. | 12/2/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: This switch must be present for auxiliary lowering to function. | 12/2/2022 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. Take corrective action as needed. | 5/13/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | No | No | Clean the car top | 8/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust upthrust roller bearings for proper clearance to door hangar track (multiple floors). | 8/29/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Trips to location are not being properly documented. | 8/29/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. The phone dials out then hangs up. | 9/6/2024 |