ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.11.2.3.2
|
Yes
|
Yes
|
An excessive amount of wear was found on the governor sheave and would not allow the elevator car safeties to activate as designed. The governor shall be replaced before the elevator will be allowed to return to service. A reinspection and alteration permit is required.
|
9/6/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the microphone of this phone for proper operation and passenger safety. Reinspection required.
|
8/16/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
10/6/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed.
|
8/16/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the microphone of this phone for proper operation and passenger safety. Reinspection required.
|
3/24/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
10/6/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
10/6/2025
|