Inspection
Inspection Details
Equipment ID
22680
22680
Inspection Date
7/9/2019
7/9/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
46e4d06c-b069-4947-81c5-c0605a8b7a57
46e4d06c-b069-4947-81c5-c0605a8b7a57
Location
Citywalk on Euclid
100 EUCLID AVE, SAINT LOUIS, MO
100 EUCLID AVE, SAINT LOUIS, MO
Owner
Mills Properties
2650 S HANLEY RD STE 200, SAINT LOUIS, MO 63144-2559
2650 S HANLEY RD STE 200, SAINT LOUIS, MO 63144-2559
Billing
Attn: Mills Properties
2650 S HANLEY RD STE 200, SAINT LOUIS, MO 63144-2559
2650 S HANLEY RD STE 200, SAINT LOUIS, MO 63144-2559
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair Basement Floor Hall sill trip Hazard | 7/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Counterweights bottom out before car reaches its final limit. Repair | 12/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be kept on site for each elevator. | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 2/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the elevator disconnects shall be unobstructed | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The door to the elevator disconnects shall be self closing & self locking | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | No flammable materials are to be stored in the elevator disconnect room | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. Previous violations from past years. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required.Previous violations from past years. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | Repair Bottom Floor Trip hazard at hall sill. Previous violation from past years. | 9/15/2025 |