Inspection
Inspection Details
Equipment ID
24536
24536
Inspection Date
7/12/2019
7/12/2019
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
John Thrasher
John Thrasher
Relief Valve Pressure
Slide
2.5
2.5
Governor Rope Pull
22/260
22/260
Door Closing Force
18
18
External ID
f5b6a8b9-a29c-4aab-8ff7-54a7c69a990f
f5b6a8b9-a29c-4aab-8ff7-54a7c69a990f
Location
Steelcote Lofts
801 Edwin Street, St. Louis, MO
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
801 Edwin Street, St. Louis, MO
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Owner
Attn: Chris Anderson
Steelcote Lofts, LLC
8040 Teasdale Ave, St. Louis, MO 63130
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Steelcote Lofts, LLC
8040 Teasdale Ave, St. Louis, MO 63130
Phone: (314) 616-2196
Email: chris@pinnaclecontracting.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | x | Provide 19 ft at the floor level in front of control on top floor. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | x | Bevel all ledges at 4" or greater. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.1 | x | Seal all hoistway penetration. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | x | Glass in rear hoistway wall shall be laminated ANSI Z97 rated and etched. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | x | Sump pump shall be 3000 GPM or larger and not tied directly to the sewer. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Install ABC fire extinguisher on car top. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 2.1.5 | x | Hoistway signage shall be permanent and read ELEVATOR HOISTWAY. | 7/17/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No current maintenance records on site. | 9/29/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No current operating certificate on display. | 9/29/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor does not work. | 6/24/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor does not work. Repair or replace 8.6.4.13.1 (l) | 9/12/2023 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Need to clean pit to remove debris, water and /or oil and address sources | 2/28/2024 | ||
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Car door restrictor does not work, needs repaired. Re-inspection required | 7/29/2024 |