Inspection
Inspection Details
Equipment ID
14396
14396
Inspection Date
7/23/2019
7/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Kevin Crossland
Kevin Crossland
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
FR 23 R 22
FR 23 R 22
External ID
793dc381-0e4f-4d10-b9e3-cc0ae3e7cec7
793dc381-0e4f-4d10-b9e3-cc0ae3e7cec7
Location
HAAS Warehouse Renovation
201 N WASHINGTON ST, NEOSHO, MO
201 N WASHINGTON ST, NEOSHO, MO
Owner
Philip T Edwards
PO BOX 2708, JOPLIN, MO 64803-2708
PO BOX 2708, JOPLIN, MO 64803-2708
Billing
Attn: Philip T Edwards
PO BOX 2708, JOPLIN, MO 64803-2708
PO BOX 2708, JOPLIN, MO 64803-2708
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | 620.85 Needs GFCI in machine room | 8/4/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | 620.53 NEC machine room needs GFCI recepticle | 8/4/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted | 8/4/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher has,t been checked since 2017 | 8/4/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | 620-85 Needs GFCI in machine room. (REINSPECTION WITHIN 30 days) Multi-year violation. | 8/4/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 2013 displayed | 8/4/2021 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher has,t been checked since 2017 | 1/20/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK(with and w/o main power) and give proper location. Dials but doesn't connect. Replace phone battery also. (REINSPECTION 14days to REDTAG) | 8/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in machine room | 9/20/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting bulbs shall be protected | 9/20/2023 |