Inspection
Inspection Details
Equipment ID
1447
1447
Inspection Date
7/19/2019
7/19/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
f70f57c0-2acf-491f-9bbd-030c6c12c885
f70f57c0-2acf-491f-9bbd-030c6c12c885
Location
Macys Midwest
1 MID RIVERS MALL DR, SAINT PETERS, MO
1 MID RIVERS MALL DR, SAINT PETERS, MO
Owner
Attn: RICARDO FELICIANO-CRUZ
MACY'S MSOC VERTICAL COMPLIANCE
237 WOODBRIDGE CENTER DR 3rd, Woodbridge, NJ 07095
Phone: (732) 734-3439
Email: Ricardo.Feliciano-Cruz@macys.com
MACY'S MSOC VERTICAL COMPLIANCE
237 WOODBRIDGE CENTER DR 3rd, Woodbridge, NJ 07095
Phone: (732) 734-3439
Email: Ricardo.Feliciano-Cruz@macys.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Provide load class plate in car | 10/19/2018 |
| conversion | conversion | n/a | No | No | Repalce car gate interlock cover | 10/19/2018 |
| conversion | conversion | n/a | No | No | Replace missing hoistway door control box top of car | 10/19/2018 |
| conversion | conversion | n/a | No | No | Post current State certificate in machine room | 10/19/2018 |
| conversion | conversion | n/a | No | No | Clean pit | 10/19/2018 |
| conversion | conversion | n/a | No | No | Replace msiing interlock covers at LL & UL levels | 10/19/2018 |
| conversion | conversion | n/a | No | No | Repair/replace hoistway door pull stations | 10/19/2018 |
| conversion | conversion | n/a | No | No | Provide capacity plate in car | 10/19/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Repair/Replace Hoistway Door Pull Stations | 10/19/2018 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)2 | No | No | Safety edge not working on car gate (Constant pressure, not self closing doors) | 8/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 8/14/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 8/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair car gate astrical | 8/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Reinstall missing cover on upper and lower hatchdoor operators, hatch door interlocks and car door operator | 8/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing covers on LL & LU hatch door interlocks | 11/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair safety astragal on car gate | 11/12/2025 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 8.11.3.1.1(g) | No | No | Replace missing covers on LL LU level hatch door interlocks | 11/12/2025 |
| A17.1-2016 : Elevators | 1.2 - Stop Switches | 2.26.2.5 | No | No | Replace Broken Stop Switch In Car. | |
| A17.1-2016 : Elevators | 6.2 - Operation of elevators under fire and other emergency conditions (A17.1-1981 through A17.1b-1983) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | Perform Monthly Fire Service Test and Document on Log In Machine Room. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current State Certificate | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.19.15 Emergency Communications | Yes | No | Repair Means Of Two Way Communication With Car. Reinspection Required in 30 Days. |