Inspection
Inspection Details
Equipment ID
8842
8842
Inspection Date
4/25/2019
4/25/2019
Inspection Type
Other Inspection
Other Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
4119adcb-1491-4437-aa88-990eabf780b0
4119adcb-1491-4437-aa88-990eabf780b0
Location
Gallery 720
720 OLIVE ST, SAINT LOUIS, MO
720 OLIVE ST, SAINT LOUIS, MO
Owner
Attn: Brandview LLC
Brandview LLC
720 OLIVE ST APT 2720, SAINT LOUIS, MO 63101
Phone: (314) 328-7900
Email: gallery720@stlluxury.com
Brandview LLC
720 OLIVE ST APT 2720, SAINT LOUIS, MO 63101
Phone: (314) 328-7900
Email: gallery720@stlluxury.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate in the elevator machine room. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide MCP documentation. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | All machine room wiring shall be enclosed. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | All hoistway ducts shall have covers. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | The car top shall be kept clean. Clean the car top. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.8 Switch Keys (Re-Inspection) | x | The phase 1 fire service key switch located in the firemans command panel shall be operational. | 3/5/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | x | Provide code compliant runby. | 3/5/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Provide code compliant pit lighting. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post the current state operating certificate in the elevator machine room. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide MCP documentation. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | All machine room wiring shall be enclosed. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | All hoistway ducts shall have covers. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | The car top shall be kept clean. Clean the car top. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | x | Provide code compliant runby. | 10/6/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Provide code compliant pit lighting. | 9/10/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | The main disconnect shall be labeled with the source location, name, and breaker numbers. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide a code compliant MCP including onsite documents. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO state operating certificate shall be displayed in the elevator machine room. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | The machine room door shall be self-closing and self-locking. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | Materials not necessary for the operation of the elevators shall not be kept in the machine room. (Non used controllers, MG sets, and other various items) | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | Provide code compliant permanent lighting in machinery space and secondary machinery spaces. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Remove the wiring and conduit that is not being used at the 30th floor near the hall pushbutton. | 5/3/2021 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service test charts are missing. | 12/19/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | Provide a code compliant code data tag. | 12/19/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Materials not necessary for the operation of the elevator shall not be kept in the machine room. (Non-used controllers, MG sets, and various other items) | 12/19/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | The machine room door shall be self-closing and self-locking. | 12/19/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Provide proper clearance for pit lights at front of pit. | 12/19/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | The secondary machine space, where the governors are located, has insufficient lighting. The lighting in the secondary machine space shall be at least 19 foot-candles. | 10/4/2023 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Hole in hoistway wall at floor 21 shall be sealed closed. |