Inspection
Inspection Details
Equipment ID
11171
11171
Inspection Date
4/18/2019
4/18/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
375
375
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
5b6c3282-85c8-4e61-a6b4-9e0ec5d0e903
5b6c3282-85c8-4e61-a6b4-9e0ec5d0e903
Location
Pierre Laclede Center
7733 FORSYTH BLVD, CLAYTON, MO
7733 FORSYTH BLVD, CLAYTON, MO
Owner
CBRE
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
Billing
Attn: CBRE
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Car emergency telephone is not loud enough to make two way communication possible. | 4/18/2019 | |
conversion | conversion | conversion - reinspect | x | Schedule a full lad test of the emergency power system on elevators 1-8. | 4/18/2019 | |
conversion | conversion | n/a | Car emergency lighting shall work. | 10/1/2019 | ||
conversion | conversion | conversion - reinspect | x | Shorten the hoist ropes for proper up final limit switch operation. | 4/18/2019 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Test emergency power. | 7/28/2019 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 11/6/2020 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 4/26/2022 | ||
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. | 6/26/2023 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 | |
A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 211.9 | COP shall display unit identifier (Elevator #8). | 3/26/2024 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris. | 3/26/2024 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Phase 2 switch Halo and Call Cancel Halo to be replaced. It is faded and unreadable. | 3/26/2024 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |