Inspection
Inspection Details
Equipment ID
11050
11050
Inspection Date
4/16/2019
4/16/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
24"
24"
Governor Rope Pull
280/890
280/890
Door Closing Force
21
21
External ID
f8436074-c2bd-4906-a7c5-0f258e043107
f8436074-c2bd-4906-a7c5-0f258e043107
Location
Pierre Laclede Center
7701 FORSYTH BLVD, CLAYTON, MO
7701 FORSYTH BLVD, CLAYTON, MO
Owner
CBRE
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
Billing
Attn: CBRE
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | The emergency power shall be tested with 125% of capacity. | 7/28/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevators shall be operational. | 11/9/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. | 4/26/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work. Bracket is missing. | 6/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing hall fire signage. It shall read "in case of fire" (C Level). | 6/30/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing incomplete. Need to test: FS, EP, EQ, SOS, Buffers (car/CW), 100% safeties, 125% (hold & 1 floor run), slide. | 3/25/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | MCP Fire Service testing must be properly documented monthly on log sheet. | 6/30/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired state operating certificate in the machine room. | 3/25/2026 |