Inspection
Inspection Details
Equipment ID
11048
11048
Inspection Date
4/15/2019
4/15/2019
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
22"
22"
Governor Rope Pull
180/510
180/510
Door Closing Force
21
21
External ID
92a991b6-a0ad-4ba8-8e93-e024c18502b6
92a991b6-a0ad-4ba8-8e93-e024c18502b6
Location
Pierre Laclede Center
7701 FORSYTH BLVD, CLAYTON, MO
7701 FORSYTH BLVD, CLAYTON, MO
Owner
CBRE
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
7733 FORSYTH BLVD STE 295, CLAYTON, MO 63105-1817
Billing
Attn: CBRE
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
7733 FORSYTH BLVD STE 295, SAINT LOUIS, MO 63105-1817
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | The emergency power shall be tested with 125% of capacity. | 7/28/2019 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | x | Emergency/standby power operation of the elevators shall be operational. | 11/9/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. | 4/26/2022 | ||
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work at all floors. | 6/26/2023 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris & oil. | 3/19/2024 | ||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testing incomplete. Need to test: FS, EP, EQ, SOS, Buffers (car/cw), 100% safeties, 125% (hold & 1 floor run), slide. | 3/25/2024 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency lighting shall work. | 3/25/2024 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell shall work with loss of main 120v power. | 3/25/2024 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | MCP Fire service testing must be properly documented monthly on log sheet. | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Pit light shall work. | |||
A17.1-1996 : Elevators | 3.23 - Suspension rope | 212 | x | Ropes are rouged and need to be replaced. |