Inspection
Inspection Details
Equipment ID
8886
8886
Inspection Date
7/8/2019
7/8/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
319333f3-80db-43ad-b2f3-325db3036f7e
319333f3-80db-43ad-b2f3-325db3036f7e
Location
U-Haul- O'Fallon
2000 HIGHWAY K, O FALLON, MO
2000 HIGHWAY K, O FALLON, MO
Owner
Attn: UNK
U-Haul- International
PO BOX 21502, PHOENIX, AZ 85036
Phone: (000) 000-0000
U-Haul- International
PO BOX 21502, PHOENIX, AZ 85036
Phone: (000) 000-0000
Billing
Attn: U-Haul Company of St. Louis
UHaul Co of Missouri NE
12060 LUSHER RD, SAINT LOUIS, MO 63138
Phone: (000) 000-0000
Email: tammy-wittman@uhaul.com
UHaul Co of Missouri NE
12060 LUSHER RD, SAINT LOUIS, MO 63138
Phone: (000) 000-0000
Email: tammy-wittman@uhaul.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | x | In cab emergency telephone does not work, and shall be repaired and retested. | 6/12/2019 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In car emergency telephone shall work. | 7/8/2019 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/1/2021 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Security company monitoring elevator cab phone could not give the location of elevator. Program or repair phone to provide location. Re-inspection required | 11/9/2022 | |
A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | x | Teh emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspect by 7/13/23 (30 days) | 8/2/2023 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency lighting shall work. Multi-year violaton. | 9/18/2024 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm Bell shall work with loss of main 120v power. | 9/18/2024 | |
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | Non-elevator related items shall not be stored in the machine room. | 9/30/2024 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing must be documented monthly. | 9/30/2024 | ||
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | Non-elevator related items shall not be stored in the machine room. | 9/30/2024 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing must be documented monthly. Note: Last documented test was the June 2024 annual inspection. | 9/30/2024 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing must be documented monthly | 7/16/2025 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Car lighting disconnect in machine room requires a proprietary key which was not found in the room. Provide key to be left in machine room. | 7/16/2025 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/16/2025 |