Inspection
Inspection Details
Equipment ID
1623
1623
Inspection Date
7/23/2019
7/23/2019
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
d56b0361-9419-4e2f-8b83-d1d0f8e7d654
d56b0361-9419-4e2f-8b83-d1d0f8e7d654
Location
Locust Street Administration Building
220 LOCUST ST, WASHINGTON, MO
Phone: (000) 000-0000
220 LOCUST ST, WASHINGTON, MO
Phone: (000) 000-0000
Owner
School District of Washington
220 LOCUST ST, WASHINGTON, MO 63090-2829
220 LOCUST ST, WASHINGTON, MO 63090-2829
Billing
Attn: School District of Washington
2160 HIGHWAY A, WASHINGTON, MO 63090-6425
2160 HIGHWAY A, WASHINGTON, MO 63090-6425
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 10/26/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The emergency light fixture inside the elevator is not operational and shall be repaired. | 10/26/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 7/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 7/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The slack rope switches in the pit fail to activate when the elevator safeties are set and the hoist rope becomes slack. Slack rope switches shall be adjusted to operate as designed | 9/17/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)5 | Yes | Yes | The slack rope switches in the pit fail to activate when the elevator safeties are set and the hoist rope becomes slack. Slack rope switches shall be adjusted to operate as designed | 9/3/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency lowering device not working | 11/20/2023 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency lighting shall work. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering shall work. Repair or replace. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | MCP fire service testing must be properly documented monthly on log sheet. Logs are blank. |