Inspection
Inspection Details
Equipment ID
9431
9431
Inspection Date
7/25/2019
7/25/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Healy
David Healy
Mechanic Name
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
22/25
22/25
External ID
c3a715a5-932e-42a3-9aca-e0a98550f66b
c3a715a5-932e-42a3-9aca-e0a98550f66b
Location
Bates County Courthouse
1 N DELAWARE ST, BUTLER, MO
1 N DELAWARE ST, BUTLER, MO
Owner
Bates County of
1 N DELAWARE ST, BUTLER, MO 64730-2266
1 N DELAWARE ST, BUTLER, MO 64730-2266
Billing
Attn: Bates County of
1 N DELAWARE ST, BUTLER, MO 64730-2266
1 N DELAWARE ST, BUTLER, MO 64730-2266
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | emergency light and bell failed | 1/16/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | no testing procedures no valve info | 7/31/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current city. Posted | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Battery lowering not working | 1/19/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(c)(5) | No | No | Need test procedure for overspeed valve | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | both car doors open or closed from either set of car buttons at same time at floor with opposed openings | 1/19/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Emg Battery lowering not working | 7/8/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | when at a floor with both front an rear doors at that foor both front an rear doors open at the same time. | 7/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit lt not working | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | couldnt test emg power at time of insp | 6/13/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | fire ext. out of date needs checked annually |