Inspection
Inspection Details
Equipment ID
2124
2124
Inspection Date
7/23/2019
7/23/2019
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
James Burke
James Burke
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
0de3414b-6a06-48b9-8e7c-4fc59532913b
0de3414b-6a06-48b9-8e7c-4fc59532913b
Location
Conception Abbey
37174 STATE HIGHWAY VV, CONCEPTION, MO
37174 STATE HIGHWAY VV, CONCEPTION, MO
Owner
Conception Abbey
37174 STATE HIGHWAY VV, CONCEPTION, MO 64433-8102
37174 STATE HIGHWAY VV, CONCEPTION, MO 64433-8102
Billing
Attn: Conception Abbey
37174 STATE HIGHWAY VV, CONCEPTION, MO 64433-8102
37174 STATE HIGHWAY VV, CONCEPTION, MO 64433-8102
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. | 7/31/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines need to removed from tank. Cylinder drain lines need to drain into seperate pit containers that are covered and no more than 5 gallon capacity. | 3/23/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. Need to provide pit lighting. | 3/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines run back to storage tank. Remove from storage tank and install in pit collection containers | 9/16/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Install covers on 4x4 junction boxes located on hoistway wall. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No electrical power at light fixture. Need to provide power to pit light fixture. | 9/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Cylinder drain lines shall be ran to pit collection container and not the hydraulic storage tank in the machine roo.. | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate. No power at light fixture. Circuit breaker or wiring issue. | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | ADJUST DOOR RESTRICTOR SO IT WORKS | 7/8/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | REPLACE SUMP PUMP COVER ( IT IS IN THE PIT) | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | REMOVE STANDING OIL FROM PIT | 9/16/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | REDUCE THE CLOSING FORCE TO <30 LBS | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | CLEAN OIL FROM PIT FLOOR AND REPAIR LEAK | 9/16/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | INSTALL SUMP COVER | 9/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | INSTALL A SELF CLOSER ON MACHINE ROOM DOOR |